Home / Fire protection coatings

Fire protection coatings for steel structures R15 to R120: in our Senec workshop and on site

In Senec we apply fire protection (intumescent) coatings to steel structures before erection. We provide protection for both cellulosic and hydrocarbon fire scenarios, with fire resistance from R15 to R120. We are an Approved Applicator of FIRETEX FX6002 (Sherwin-Williams). We have applied Chartek 2218 (International, AkzoNobel) on site at the Evonik plant in Slovenská Ľupča. For the ESMC plant in Dresden we coated approx. 28,000 m² of steelwork to fire resistance R90 in this way. Besides coatings, we also spray Perlifoc HP fire-resistant mortar (Carboline).

Spray application in the Senec paint shop
Spray application in the Senec paint shop

Shop application instead of on-site application

Components are coated in a hall where we record temperature, humidity and dew point for every coat. The thickness of the fire protection layer is measured on every component. The steelwork arrives on site with the coating already completed.

In our Senec workshop we handle components up to 26 × 5 × 5 m and 33 t.

Fire resistance
R15–R120
Largest component in Senec
26 × 5 × 5 m
weight up to 33 t
Extracted spray booth in the Senec hall
Extracted spray booth in Senec

How a fire protection coating works

Steel temperature
  1. Normal conditionsA thin coating on the steel beam.
  2. FireThe coating swells and forms an insulating layer.
  3. ProtectionThe steel heats up more slowly. The beam holds for R15 to R120.
Illustrative diagram.
Cellulosic fire

FIRETEX FX6002

FIRETEX FX6002 is a three-component intumescent coating with very fast drying. In a fire it expands and protects the steel from overheating.

ParameterValue
Fire scenariocellulosic
Fire resistanceup to 120 minutes (R15 to R120), depending on section and thickness
Testing and assessmentEN 13381-8, European Technical Assessment ETA 20/1261
Germanyallgemeine Bauartgenehmigung DIBt Z-19.51-2672
PrimerMacropoxy 400
Topcoatdepending on the environment, e.g. Acrolon EG-5
Our approvalApproved Applicator FIRETEX FX6002, Sherwin-Williams Coatings Deutschland, valid until November 2027

Coating thicknesses are specified by the coating supplier for each section according to its dimensions and the required R class.

We apply cellulosic fire protection coatings such as FIRETEX with two new Graco XP70-HF units.

Hydrocarbon fire

Hydrocarbon fire: Chartek

Chartek is an epoxy intumescent coating by International (AkzoNobel) for protecting steel against hydrocarbon fires, i.e. the burning of oil, gas and chemicals. It is used in refineries, chemical plants and gas facilities. We applied Chartek 2218 at the Evonik plant in Slovenská Ľupča.

ParameterValue
Fire scenariohydrocarbon, depending on the product also jet fire
Materialtwo-component epoxy intumescent coating, high film build
Protectionfire and corrosion protection in one system
Reinforcementmesh as per design, where required by the fire protection design

Chartek is applied in accordance with the manufacturer's application manual. We apply hydrocarbon fire protection coatings with Graco XM PFP units.

Procedure and inspection

  1. Blast cleaningBlast cleaning with GH40 steel grit to grade Sa 2½ in accordance with EN ISO 8501-1, surface profile check in accordance with EN ISO 8503.
  2. PrimerPrimer according to the fire protection coating manufacturer's system.
  3. Fire protection layerFire protection layer at the thickness specified by the supplier, for hydrocarbon fire with reinforcing mesh where required by the design.
  4. TopcoatTopcoat according to the environment.

For every coat we record air and substrate temperature, humidity, dew point and material batch numbers. Thickness is measured at several points on each component and the results are handed over in an inspection record in Slovak and English. On request, our FROSIO Level III inspector carries out an inspection.

Reference: ESMC Dresden

We coated the steel structures for the ESMC semiconductor plant in Dresden in Senec and shipped them to the construction site in Germany.

ParameterValue
Areaapprox. 28,000 m²
Surface preparationblast cleaning with GH40 steel grit, Sa 2½
SystemMacropoxy 400 80 µm + FIRETEX FX6002 + Acrolon EG-5 topcoat
Average thicknessapprox. 2 mm
Fire resistanceR90
Period2025–2026
Visualisation of the ESMC plant in Dresden
ESMC plant Dresden, illustrative visualisation

Reference: Evonik, Slovenská Ľupča

At the Evonik plant in Slovenská Ľupča we applied a fire protection coating for the hydrocarbon fire scenario.

ParameterValue
Areaapprox. 2,000 m²
MaterialChartek 2218
Average thicknessapprox. 2 mm
Fire scenariohydrocarbon
Evonik, Slovenská Ľupča
Evonik, Slovenská Ľupča

Reference: Jaguar Land Rover Nitra, BIW2 hall

For PROMONT, we spray-applied Perlifoc HP fire-resistant mortar to the steel roof structure of the BIW2 hall (Body in White Shop 2) at the Jaguar Land Rover plant in Nitra, for fire resistance R240. Perlifoc HP is a gypsum-based mortar with reaction-to-fire class A1 according to EN 13501-1. The manufacturer tested it on steel members according to EN 13381-4. We applied it with our own Graco ToughTek MP260 mixing pump.

ParameterValue
CustomerPROMONT
Substratesteel roof structure
Areaapprox. 6,000 m²
MaterialPerlifoc HP (Carboline), fire-resistant mortar
Average thicknessapprox. 25 mm
Applicationmachine spraying, Graco ToughTek MP260
Fire resistanceR240
Period2026
BIW2 hall, Jaguar Land Rover Nitra
BIW2 hall, Jaguar Land Rover Nitra

Contact

Please send us a list of components with sections, surface area in m², the required R class and the thickness calculation, if available. We send a quotation within 5 working days on average.